| Ambient temperature (operation) |
-40 … +70 °C |
| Ambient temperature (storage) |
-40 … +85 °C |
| Protection type |
IP20 |
| Pollution degree |
2 per IEC 61131-2 |
| Operating altitude |
without temperature derating: 0 … 2000 m; with temperature derating: 2000 … 5000 m (0.5 K/100 m); 5000 m (max.) |
| Mounting position |
Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom |
| Relative humidity (without condensation) |
95% |
| Relative humidity (with condensation) |
Short-term condensation per Class 3K7/IEC EN 60721-3-3 and E-DIN 40046-721-3 (except for wind-driven precipitation, water and ice formation) |
| Vibration resistance |
According to type test for marine classification (ABS, BV, DNV, IACS, LR): acceleration: 5g, IEC 60068-2-6, EN 60870-2-2, IEC 60721-3-1, -3, EN 50155, EN 61373 |
| Shock resistance |
per IEC 60068-2-27 (10g/16 ms/half-sine/1,000 shocks; 25g/6 ms/half-sine/1,000 shocks), EN 50155, EN 61373 |
| EMC immunity to interference |
per EN 61000-6-1, -2; EN 61131-2; marine applications; EN 50121-3-2; EN 50121-4, -5; EN 60255-26;
EN 60870-2-1; EN 61850-3; IEC 61000-6-5; IEEE 1613; VDEW: 1994 |
| EMC emission of interference |
per EN 61000-6-3, -4, EN 61131-2, EN 60255-26, marine applications, EN 60870-2-1, EN 61850-3, EN 50121-3-2, EN 50121-4, -5 |
| Exposure to pollutants |
per IEC 60068-2-42 and IEC 60068-2-43 |
| Permissible H2S contaminant concentration at a relative humidity 75 % |
10ppm |
| Permissible SO2 contaminant concentration at a relative humidity 75 % |
25ppm |