| Supply voltage |
| Load voltage L+ |
|
| • Rated value (DC) |
24 V |
| • permissible range, lower limit (DC) |
20.4 V |
| • permissible range, upper limit (DC) |
28.8 V |
| Input current |
|
| from load voltage L+ (without load), max. |
160 mA |
| from backplane bus 5 V DC, max. |
110 mA |
| Power loss |
|
| Power loss, typ. |
6.6 W |
| Digital outputs |
|
| Number of digital outputs |
32 |
| Short-circuit protection |
Yes; Electronic |
| • Response threshold, typ. |
1 A |
| Limitation of inductive shutdown voltage to |
L+ (-53 V) |
| Controlling a digital input |
Yes |
| Switching capacity of the outputs |
|
| • on lamp load, max. |
5 W |
| Load resistance range |
|
| • lower limit |
48 Q |
| • upper limit |
4 kQ |
| Output voltage |
|
| • for signal "1", min. |
L+ (-0.8 V) |
| Output current |
|
| • for signal "1" rated value |
0.5 A |
| • for signal "1" permissible range for 0 to 40 °C, min. |
5 mA |
| • for signal "1" permissible range for 0 to 40 °C, max. |
0.6 A |
| • for signal "1" permissible range for 40 to 60 °C, min. |
5 mA |
| • for signal "1" permissible range for 40 to 60 °C, |
0.6 A |
| max. |
|
| • for signal "1" minimum load current |
5 mA |
| • for signal "0" residual current, max. |
0.5 mA |
| Output delay with resistive load |
|
| • "0" to "1", max. |
100 卩s |
| • "1" to "0", max. |
500 卩s |
| Parallel switching of two outputs |
|
| • for uprating |
No |
| • for redundant control of a load |
Yes; only outputs of the same group |
| Switching frequency |
|
| • with resistive load, max. |
100 Hz |
| • with inductive load, max. |
0.5 Hz |